What is the minimum interval between two consecutive overloads of 150% for 60 seconds for ATV31 Series Drives.

The 150% overload time is specified as 1 minute (60 sec) every 10 minutes at 40°C ambiance temperature. This means that the ATV31 Drive is allowed to run at an overload of 150% for 1 minute and there after the overload must not exceed 100% for at least the next 9 minuntes.