Compatibility - FAQs

FAQ Search
>   Select Language
Most Recently Published FAQs

Results 31 - 40 of 56

FAQ ID Description
FA12186Is it possible to do remote reset function with ASI module ASILUF05 of TeSys U.
ASILUFC5 unit works on the ASI bus which is a basic bus and handles only 31 or 62 slaves. This unit cannot support the remote reset function alone.The...
FA22772What is the difference between 31088 and 31097 key locking devices.
31097 keylocking device is used for the Single Handle Source Changeover Assembly in which different type off cam is used. These cams are to be ordered...
FA12200What is the maximum rated current for 36KV Fusarc switch.
The maximum rated current for 36KV Fusrac switch is 63 Amps. Refer attachment for the selection of proper fuse.
FA12175Can two Line Chokes be connected in series for Altivar 31/61/71 Drives, in case the correct value Line Choke is not available.
Yes, two smaller Line Chokes can be connected in series for Altivar 31/61/71 Drives.Note:The drop voltage of Line Choke is approximately 3% of the...
FA12124What is the minimum rating of the Motor that can be used with the Altivar 31/61/71 Range of Drives.
The motor current should not be less than 0.2 times the nominal Drive current when the motor is driven by Altivar 31/61/71 Drives, for thermal protection.However,...
FA12080Is it possible to install the Fusarc fuse in the upstream of LBS (Load Break Switch).
Yes, it is possible to install the Fusarc fuses in the upstream of Load Break Switch (LBS) switch. Note: 1. Refer the attached sheet to choose and...
FA12184Is it possible to install OF/SD/SDE Auxiliary Contact (29450) in Single Pole and Two Pole Compact NS MCCBs.
Auxiliary Contact installation is possible in Two Poles MCCBs same as in Three Pole and Four Pole MCCBs, but it is not possible to install and use...
FA12083What is the size of cable that can be used for the remote connection of time delayed UVR/MN module of Masterpact ACBs.
With the increase in length there always occurs a voltage drop in the cable. Refer the attachment for voltage drop values, according to cable sizes...
FA12107How the mechanical interlocking can be done between Masterpact M and Masterpact NW ACB’s by using two interlocks and one key.
To interlock the two Air Circuit Breakers (ACBs) with the same key, you need to order the Ronis keylock reference 48550 or Profalux keylock 48546.For...
FA12079What are the Spare Reference Numbers of Finger Contacts and Arms of LF2 (SF6 Breaker).
The spare reference number of Finger Contacts of LF2 (SF6 Breaker) is AAV48765. A single kit contains 6 sets of Finger clusters.However, the Arm is...

Results 31 - 40 of 56