| FA12190 | Is it possible to use LTME DC Expansion module with LTMR AC module of TeSys T. Yes, it is possible to use LTME DC Expansion module with LTMR AC module of TeSys T. |
| FA12186 | Is it possible to do remote reset function with ASI module ASILUF05 of TeSys U. ASILUFC5 unit works on the ASI bus which is a basic bus and handles only 31 or 62 slaves. This unit cannot support the remote reset function alone.The... |
| FA12203 | Can the Multi 9 range MCB be reverse fed. Yes, the Multi9 miniature circuit breakers (MCBs) can be fed either from top or bottom without any deterioration of their characteristics.
Refer... |
| FA22772 | What is the difference between 31088 and 31097 key locking devices. 31097 keylocking device is used for the Single Handle Source Changeover Assembly in which different type off cam is used. These cams are to be ordered... |
| FA12200 | What is the maximum rated current for 36KV Fusarc switch. The maximum rated current for 36KV Fusrac switch is 63 Amps. Refer attachment for the selection of proper fuse. |
| FA12175 | Can two Line Chokes be connected in series for Altivar 31/61/71 Drives, in case the correct value Line Choke is not available. Yes, two smaller Line Chokes can be connected in series for Altivar 31/61/71 Drives.Note:The drop voltage of Line Choke is approximately 3% of the... |
| FA12124 | What is the minimum rating of the Motor that can be used with the Altivar 31/61/71 Range of Drives. The motor current should not be less than 0.2 times the nominal Drive current when the motor is driven by Altivar 31/61/71 Drives, for thermal protection.However,... |
| FA12080 | Is it possible to install the Fusarc fuse in the upstream of LBS (Load Break Switch). Yes, it is possible to install the Fusarc fuses in the upstream of Load Break Switch (LBS) switch. Note: 1. Refer the attached sheet to choose and... |
| FA12087 | Provide the maximum length of cable that can be used with Multi9 circuit breakers in TN Network. Refer attached document for the Maximum length of cable that can be used with Multi9 circuit breakers in TN Network. |
| FA12183 | What is the latest Feature and Reference Number of MA500 trip unit for Compact NS630 MCCB. The new name of the MA500 trip unit is MAE500 or STR13MAE500.The old MA500 trip unit was designed with mechanical feature and new MA trip unit is... |