FAQ ID Description
FA12213Is it possible to use TeSys GV2 and TeSys GV3 Range MPCB in DC applications.
The TeSys GV2 and TeSys GV3 range MPCB can be used in DC applications as per their technical specifications.  Refer the below wiring connection for...
FA12210What is the maximum DC voltage per pole for TeSys D range contactors.
The maximum DC voltage for TeSys D range contactor is 75 Volt per pole. This voltage is applicable for the specification of L/R
FA12192Is it possible to control the motor from TeSys T via the PowerSuite software.
The configuration of TeSys T, read diagnostic, parameter setting and custom logic development is possible via PowerSuite software.However, the controls...
FA12195What is the total power dissipation per pole in watts of Vario Switches at the specified Thermal Current Rating (Ith).
The total power dissipation per pole in Watts of Vario Switches at the specified Thermal Current Rating (Ith) is as tabulated below: ...
FA12191Is it possible to connect the different control voltages at the input of LTMR module in TeSys T.
Control Voltage characteristics You can connect different control voltages on the input of the LTMR TeSys T module, if the voltage and current ratings...
FA12203Can the Multi 9 range MCB be reverse fed.
Yes, the Multi9 miniature circuit breakers (MCBs) can be fed either from top or bottom without any deterioration of their characteristics.   Refer...
FA12158Is it possible to have dual connections from the Altivar 31 Drive ModBus Port.
Yes, it is possible to have dual connections from a single Altivar 31 Drive ModBus Port, one for connection to the ModBus Communication Network and...
FA11929How to install the USB driver for Zelio Soft2 and install USB cable SR2USB01.
Follow the step by step procedure in order to install the USB driver for Zelio Soft2 and the USB cable SR2USB01 for two different operating systems...
FA12163What is the minimum DC voltage level to power up the Altivar 61/71 Drive via DC Bus.
The minimum DC Voltage level required to power up the Altivar 61/71 Drive via DC Bus is 537VDC. The DC Bus Voltage = √2 * Uln (Square Root of 2 multiplied...
FA12091What does the Counters 22, 2C, 2E, 2F depict in FIPIO Communication.
Counter 2Eh (Number of Pierced Frame Fault): This counter allows diagnoses of the receipt of a silent inside a frame i.e. between the identification...