| FA12203 | Can the Multi 9 range MCB be reverse fed. Yes, the Multi9 miniature circuit breakers (MCBs) can be fed either from top or bottom without any deterioration of their characteristics.
Refer... |
| FA12158 | Is it possible to have dual connections from the Altivar 31 Drive ModBus Port. Yes, it is possible to have dual connections from a single Altivar 31 Drive ModBus Port, one for connection to the ModBus Communication Network and... |
| FA11929 | How to install the USB driver for Zelio Soft2 and install USB cable SR2USB01. Follow the step by step procedure in order to install the USB driver for Zelio Soft2 and the USB cable SR2USB01 for two different operating systems... |
| FA12163 | What is the minimum DC voltage level to power up the Altivar 61/71 Drive via DC Bus. The minimum DC Voltage level required to power up the Altivar 61/71 Drive via DC Bus is 537VDC. The DC Bus Voltage = √2 * Uln (Square Root of 2 multiplied... |
| FA12091 | What does the Counters 22, 2C, 2E, 2F depict in FIPIO Communication. Counter 2Eh (Number of Pierced Frame Fault): This counter allows diagnoses of the receipt of a silent inside a frame i.e. between the identification... |
| FA12124 | What is the minimum rating of the Motor that can be used with the Altivar 31/61/71 Range of Drives. The motor current should not be less than 0.2 times the nominal Drive current when the motor is driven by Altivar 31/61/71 Drives, for thermal protection.However,... |
| FA12172 | What is the Temperature Threshold at which the Cooling Fan of Altistart 48 Soft Starter start and stop is controlled. The Temperature Thresholds at which the Cooling Fan of Altistart 48 Soft Starter start and stop is controlled are as follows: 1. Start – Heatsink... |
| FA12134 | What is the Short Circuit Current Rating for Altistart 48 Range of Soft Starters for 415 Volt (Q series) and 690 volt(Y series). The Short Circuit Current Rating (SCCR) for Altistart 48 Range of Soft Starters is as follows: For Q series: 1. SCCR for ATS 48D17x to ATS 48C32x... |
| FA12155 | How to change the languages and the default Telemecanique Logo on the Keypad display for Altivar 61/71 Drives. The software required for changing the languages and the default Telemecanique Logo on the Keypad display for Altivar 61/71 Drives is Keypad Flash... |
| FA12157 | Is the braking transistor inbuilt in Altivar 71 Drives. The Braking transistor is inbuilt in maximum ratings of Altivar 71 Drive. The following Altivar 71 Drive ranges ATV71HpppM3, ATV71HpppM3X, ATV71H075N4…HC16N4,... |