Operating System - FAQs

FAQ Search
>   Select Language
Most Recently Published FAQs

Results 31 - 40 of 53

FAQ ID Description
FA12191Is it possible to connect the different control voltages at the input of LTMR module in TeSys T.
Control Voltage characteristics You can connect different control voltages on the input of the LTMR TeSys T module, if the voltage and current ratings...
FA11929How to install the USB driver for Zelio Soft2 and install USB cable SR2USB01.
Follow the step by step procedure in order to install the USB driver for Zelio Soft2 and the USB cable SR2USB01 for two different operating systems...
FA12163What is the minimum DC voltage level to power up the Altivar 61/71 Drive via DC Bus.
The minimum DC Voltage level required to power up the Altivar 61/71 Drive via DC Bus is 537VDC. The DC Bus Voltage = √2 * Uln (Square Root of 2 multiplied...
FA12091What does the Counters 22, 2C, 2E, 2F depict in FIPIO Communication.
Counter 2Eh (Number of Pierced Frame Fault): This counter allows diagnoses of the receipt of a silent inside a frame i.e. between the identification...
FA12124What is the minimum rating of the Motor that can be used with the Altivar 31/61/71 Range of Drives.
The motor current should not be less than 0.2 times the nominal Drive current when the motor is driven by Altivar 31/61/71 Drives, for thermal protection.However,...
FA12172What is the Temperature Threshold at which the Cooling Fan of Altistart 48 Soft Starter start and stop is controlled.
The Temperature Thresholds at which the Cooling Fan of Altistart 48 Soft Starter start and stop is controlled are as follows: 1. Start – Heatsink...
FA12134What is the Short Circuit Current Rating for Altistart 48 Range of Soft Starters for 415 Volt (Q series) and 690 volt(Y series).
The Short Circuit Current Rating (SCCR) for Altistart 48 Range of Soft Starters is as follows: For Q series: 1. SCCR for ATS 48D17x to ATS 48C32x...
FA12155How to change the languages and the default Telemecanique Logo on the Keypad display for Altivar 61/71 Drives.
The software required for changing the languages and the default Telemecanique Logo on the Keypad display for Altivar 61/71 Drives is Keypad Flash...
FA12157Is the braking transistor inbuilt in Altivar 71 Drives.
The Braking transistor is inbuilt in maximum ratings of Altivar 71 Drive. The following Altivar 71 Drive ranges ATV71HpppM3, ATV71HpppM3X, ATV71H075N4…HC16N4,...
FA12080Is it possible to install the Fusarc fuse in the upstream of LBS (Load Break Switch).
Yes, it is possible to install the Fusarc fuses in the upstream of Load Break Switch (LBS) switch. Note: 1. Refer the attached sheet to choose and...

Results 31 - 40 of 53