Options and Accessories - FAQs

FAQ Search
Most Recently Published FAQs

Results 51 - 60 of 61

FAQ ID Description
FA22589Can the existing Full Function Test Kit (FFTK) be used for testing the new Compact NSX MCCB.
Compact NSX can be tested with a new dedicated test kit, Maintenance case ref erence TRV00910. This TRV00910 test kit works in association with the...
FA12121Which are the Drives in Altivar 31 Standard Range that has in-built Fan Units.
All the Drives in the Altivar 31 Standard Range has in-built Fan Units, except ATV31H018M2, ATV31H037M2, ATV31H055M2 and ATV31H075M2 Drives do not...
FA22656Is it possible to mount a surge suppressor with LED (LAD4RCE) on the CA4KN**, low consumption DC control relay.
CA4KN** control contactor comes fitted with integrated surge suppressor (bidirectional diode), thus there is no need for an external surge suppressor.   However...
FA12109How to connect the Vigi Module with Compact NS MCCB.
Refer the Vigi Installation Guide for the instruction to connect the Vigi module on the Compact NS Moulded Case Circuit Breaker (MCCB).  Caution:...
FA22592Will there be any problem if the MX coil (shunt trip) of NS100 to NS630 is continuously kept powered up.
With the newer design technology there will be absolutely no problems if the MX coil (shunt trip coil) of NS100 to NS630 is continuously kept powered...
FA12106What is the minimum distance required for cable interlocking between two Masterpact ACB’s.
Masterpact Air circuit Breaker (ACB) could be placed just side by side, there is no safety clearance required for cable interlocking between two Masterpact...
FA22594Does USB Maintenance Interface TRV00911 need calibration.
The Maintenance Interface TRV00911 does not need any calibration before the Testing of Compact NSX.   Refer the attached document as Declaration of...
FA22588Is it necessary to use the protection shield on the top side of the Compact NS>630 if the breaker is mounted in horizontal position.
The white protection shield at the top side of the breaker is for protection and isolation of the bare cable connectors against gas exhaust.   Hence...
FA22612What is the voltage tolerance level at nominal voltage for the electrical auxiliaries used in Low Voltage Circuit Breakers
The voltage tolerance level for the electrical auxiliaries (example: undervoltage release(Mn), shunt coil(Mx)) used in Low Voltage Circuit Breakers...
FA22779What is the behavior of the EM9 monitoring device if the Neutral & Earth terminals are directly connected.
EM9 Insulation monitoring device (IMD) is used on IT network system. In IT network system Neutral is isolated from Earth. EM9 measure the insulation...