| FA12165 | What is the Line dip Ride Through time for the Altivar 71 and Altivar 61 Drives. Maximum running time (without fault) at Under Voltage with Nominal Torque is: 1. 1000 msec. with a voltage 70% of nominal voltage (UrEs). 2. 500msec.... |
| FA22631 | What is the reference of Type A or Type B thermostat in Prisma Plus switchboard. Type C thermostat is available in Prisma Plus, the part reference of which is 08998. The Type C thermostat Reference 08998 can be used as Type A or... |
| FA22637 | What are the specifications of CRa, CRb & CRc sensors used in SM6 circuit breaker with their part references.
Refer the below table for the specification of the sensors:
Note: CRa/CRb/CRc sensors are not commercialized components. These sensors are... |
| FA22638 | What is the amount of SF6 gas in 24 kV SF Circuit Breaker range. In 24 KV SF Circuit Breaker range, the weight of the SF6 gas per pole for different Circuit Breakers is as follows:
SF1 Type 1 – 49 grams
... |
| FA22632 | Does Prisma Plus Switchboard confirm the Electrical continuity of moving parts. The Prisma Plus confirms the electrical continuity of moving parts as per IEC/EN 60439.1
Find attached the Declaration of Conformity for the same.
|
| FA12164 | What is the maximum operating altitude for Altivar 71 Drives. Altivar 71 Drives are designed to operate for altitude up to 3000 Meters.Note: The maximum operating altitude is 1000 Meters, after which you have... |
| FA22615 | What is the thermal class temperature for coil of CT Contactor. The thermal class temperature for coil of CT contactor is 180 Degrees Centigrade. |
| FA22627 | Can impulse-type power supply be used for electrical opening and closing order of Compact NS MCCB. Yes, the impulse-type power supply (time duration > 20 ms and Voltage level above 0.7Un) can be used for electrical opening and closing of Compact... |
| FA22628 | Is it possible to get the Earth Fault alarm only without tripping in Compact NSX with Micrologic 6, via Modbus communication. Yes, only the Earth Fault alarm can be achieved in Compact NSX with Micrologic 6A/6E without tripping the MCCB at Earth Fault.
For this, Ground... |
| FA12200 | What is the maximum rated current for 36KV Fusarc switch. The maximum rated current for 36KV Fusrac switch is 63 Amps. Refer attachment for the selection of proper fuse. |